English 中文
   Products
iTrust Industry Series industrial Your present location:Home > Products > UPSpower > Emerson > iTrust Industry Series industrial 
iTrust Industry Series UPS...


the iTrust Industry Series UPS


        Emerson Network Power iTrust Industry UPS to provide you with state-of-the-art design, easy to operate and easy to maintain, high quality new UPS power. This model is a direct match with the user's existing 220-volt battery powered systems use three-phase 380-volt input, single-phase 220 volt output of high-power uninterruptible power supply. Includes 30kVA, 40kVA,

60kVA, 80kVA four models.

Product Features:

1 large-screen LCD display in English

2. Completely electrically isolated from standard input, output isolation transformer, respectively, with the electrical input power and load isolation, mentioning

3. Stability and reliability of the UPS.

4 built-in blocking diode to avoid external diode AC and DC common cabinet security risks.

5.Advanced battery management system (battery configuration independent), which greatly improve the efficient use of the battery and extend battery life.

6.N +1 fan cooling system, even if the fan failure, redundant cooling system is still able to ensure that the system is loaded with work.

7. Redundant power, redundant work were taken from the mains, bypass, battery power, and reliable control system to ensure that the entire UPS.

8. "N +1" no cabinet directly in parallel, easy to implement and dryer and expansion, "N +1" direct machine without the use of and Cabinets



Rated output power 30kVA 40kVA 60kVA 80kVA
Physical parameters
Dimensions (W × D × H mm) 900 × 875 × 1900 900 × 875 × 1900 1250 × 875 × 1900 1250 × 875 × 1900
Weight (kg) 750 850 1150 1350
Input characteristics
Input voltage 380V, 3-phase, 4-wire
Permissible mains voltage range of +20%, -15%, adjustable supremacy of ± 25%
Frequency of 50Hz, ± 10%
Output characteristics
Output voltage of 220V, single-phase
Overload 110%, 60 minutes;
125%, 10 minutes;
150%, 1 min.
290% of rated current of inverter short circuit current limiting capability five seconds
Frequency 50Hz
Mains synchronization tracking the frequency range of ± 1Hz, ± 2Hz (adjustable)
The stability of the internal clock ± 0.1%
Voltage Stability
Steady state ± 1%
Transient ± 4% (0-100% load in 20 milliseconds recovery to the steady state value)
With linear load <2%
≤ 3% with non-linear load
53-65dB of noise (at 1 meter)


All rights reserved © Beijing constant day age electrical technology co., LTD
Tech support: huadanet 京ICP备12033506号-1